IP66 protection level
AC&DC SPD type II, always guarding the inverter
AFCI optional
Smart IV Curve scan for early panel diagnosis
Robust back-up ability, switch over time <10ms, up to 150% EPS output for 10s
Support off-grid operation
Maximum 200% PV input
Maximum 40A input current per MPpT, support high power solar panel
AI ready, forecasting solar generation and load consumption, smart energy management strategy*
VPP ready, SolaX cloud supports resource aggregator (2030.5, OpenADR )
Support smart scene function, intelligent loads management(e.g., Heat pump, EV charger)*
Micro-grid ready, supporting a variety of scenarios, both on-grid and off-grid, balancing power between PCS and Hybrid in real time
Support 7x24h scheduling mode
Support Wireless meter solution
Dual independent battery ports are ready to expand more capacity
It offers 24/7 smart energy management, utilizing AI to forecast solar generation and load consumption, with VPP readiness and intelligent scene functions for optimal energy use. It delivers high efficiency and reliability with a switch-over time of less than 10ms and up to 150% EPS output for 10 seconds, supporting off-grid operations. Additionally, it is highly cost-effective, supporting up to 200% PV input and 40A input current per MPPT, making it ideal for high-power solar panels and ensuring maximum energy savings and efficiency.
X3-AELIO-49.9K | |
PV INPUT | |
Max. recommended PV array power | 100 kWp |
Max. PV input voltage① | 1000 V |
Nominal PV input voltage | 650 V |
MPPT voltage range② | 160 ~ 950 V |
Start-up voltage | 200 V |
No. of MPP trackers / Strings per MPP tracker | 5 / 2 |
Max. input current per MPPT | 40 A |
Max. input short circuit current per MPPT | 50 A |
AC INPUT & OUTPUT (ON-GRID) | |
Rated output power | 49.9 kW |
Rated output current | 72.3 A(72.0 A) |
Max. output apparent power | 49.9 kVA |
Max. output continuous current | 83.2 A(76.0 A) |
Nominal AC voltage | 3 / N / PE, 220 / 380 V 3 / N / PE, 230 / 400 V |
Nominal AC frequency | 50 Hz / 60 Hz |
AC frequency range③ | 50 ± 5 Hz / 60 ± 5 Hz |
Adjustable Power Factor range | ~ 1 (0.8 lagging to 0.8 leading) |
THDi (rated power) | < 3% |
BATTERY | |
Battery type | Lithium |
Battery voltage range | 180 ~ 820 V |
Max. charge / discharge current | 160 A (80 A × 2) |
EPS (OFF-GRID) OUTPUT | |
Rated EPS output voltage, frequency | 230 / 400 V, 220 / 380 V, 50 Hz / 60 Hz |
Rated EPS output power | 49.9 kVA |
Peak EPS output power | 55 kVA, continuous 75 kVA, 10s |
Switchover time | < 10 ms |
EFFICIENCY | |
Max. efficiency | 98.0% |
European efficiency | 97.2% |
ENVIRONMENT LIMIT | |
Ingress protection | IP66 |
Operating ambient temperature range④ | -35 ~ 60°C |
Max. operating altitude | 3000 m |
Relative humidity | 0 ~ 100% RH (condensing) |
Overvoltage Category | Mains: Ⅲ, Battery: Ⅱ, PV: Ⅱ |
GENERAL | |
Dimensions (W × H × D) | 820 × 670 × 257 mm |
Net weight | < 100 kg |
X3-AELIO-49.9K-P | |
PV INPUT | |
Max. recommended PV array power | 120 kWp |
Max. PV input voltage① | 1000 V |
Nominal PV input voltage | 650 V |
MPPT voltage range② | 160 ~ 950 V |
Start-up voltage | 200 V |
No. of MPP trackers / Strings per MPP tracker | 6 / 2 |
Max. input current per MPPT | 40 A |
Max. input short circuit current per MPPT | 50 A |
AC INPUT & OUTPUT (ON-GRID) | |
Rated output power | 49.9 kW |
Rated output current | 72.0 A |
Max. output apparent power | 49.9 kVA |
Max. output continuous current | 76.0 A |
Nominal AC voltage | 3 / N / PE, 220 / 380 V 3 / N / PE, 230 / 400 V |
Nominal AC frequency | 50 Hz / 60 Hz |
AC frequency range③ | 50 ± 5 Hz / 60 ± 5 Hz |
Adjustable Power Factor range | ~ 1 (0.8 lagging to 0.8 leading) |
THDi (rated power) | < 3% |
BATTERY | |
Battery type | Lithium |
Battery voltage range | 180 ~ 820 V |
Max. charge / discharge current | 160 A (80 A × 2) |
EPS (OFF-GRID) OUTPUT | |
Rated EPS output voltage, frequency | 230 / 400 V, 220 / 380 V, 50 Hz / 60 Hz |
Rated EPS output power | 49.9 kVA |
Peak EPS output power | 55 kVA, continuous 75 kVA, 10s |
Switchover time | < 10 ms |
EFFICIENCY | |
Max. efficiency | 98.0% |
European efficiency | 97.2% |
ENVIRONMENT LIMIT | |
Ingress protection | IP66 |
Operating ambient temperature range④ | -35 ~ 60°C |
Max. operating altitude | 3000 m |
Relative humidity | 0 ~ 100% RH (condensing) |
Overvoltage Category | Mains: Ⅲ, Battery: Ⅱ, PV: Ⅱ |
GENERAL | |
Dimensions (W × H × D) | 820 × 670 × 257 mm |
Net weight | < 105 kg |
X3-AELIO-50K | |
PV INPUT | |
Max. recommended PV array power | 100 kWp |
Max. PV input voltage① | 1000 V |
Nominal PV input voltage | 650 V |
MPPT voltage range② | 160 ~ 950 V |
Start-up voltage | 200 V |
No. of MPP trackers / Strings per MPP tracker | 5 / 2 |
Max. input current per MPPT | 40 A |
Max. input short circuit current per MPPT | 50 A |
AC INPUT & OUTPUT (ON-GRID) | |
Rated output power | 50 kW |
Rated output current | 72.5 A(72.2A) |
Max. output apparent power | 55 kVA |
Max. output continuous current | 83.3 A(83.6A) |
Nominal AC voltage | 3 / N / PE, 220 / 380 V 3 / N / PE, 230 / 400 V |
Nominal AC frequency | 50 Hz / 60 Hz |
AC frequency range③ | 50 ± 5 Hz / 60 ± 5 Hz |
Adjustable Power Factor range | ~ 1 (0.8 lagging to 0.8 leading) |
THDi (rated power) | < 3% |
BATTERY | |
Battery type | Lithium |
Battery voltage range | 180 ~ 820 V |
Max. charge / discharge current | 160 A (80 A × 2) |
EPS (OFF-GRID) OUTPUT | |
Rated EPS output voltage, frequency | 230 / 400 V, 220 / 380 V, 50 Hz / 60 Hz |
Rated EPS output power | 50.0 kVA |
Peak EPS output power | 55 kVA, continuous 75 kVA, 10s |
Switchover time | < 10 ms |
EFFICIENCY | |
Max. efficiency | 98.0% |
European efficiency | 97.2% |
ENVIRONMENT LIMIT | |
Ingress protection | IP66 |
Operating ambient temperature range④ | -35 ~ 60°C |
Max. operating altitude | 3000 m |
Relative humidity | 0 ~ 100% RH (condensing) |
Overvoltage Category | Mains: Ⅲ, Battery: Ⅱ, PV: Ⅱ |
GENERAL | |
Dimensions (W × H × D) | 820 × 670 × 257 mm |
Net weight | < 100 kg |
X3-AELIO-60K | |
PV INPUT | |
Max. recommended PV array power | 120 kWp |
Max. PV input voltage① | 1000 V |
Nominal PV input voltage | 650 V |
MPPT voltage range② | 160 ~ 950 V |
Start-up voltage | 200 V |
No. of MPP trackers / Strings per MPP tracker | 6 / 2 |
Max. input current per MPPT | 40 A |
Max. input short circuit current per MPPT | 50 A |
AC INPUT & OUTPUT (ON-GRID) | |
Rated output power | 60 kW |
Rated output current | 87.0 A(86.6A) |
Max. output apparent power | 66 kVA |
Max. output continuous current | 100.0 A(100.3A) |
Nominal AC voltage | 3 / N / PE, 220 / 380 V 3 / N / PE, 230 / 400 V |
Nominal AC frequency | 50 Hz / 60 Hz |
AC frequency range③ | 50 ± 5 Hz / 60 ± 5 Hz |
Adjustable Power Factor range | ~ 1 (0.8 lagging to 0.8 leading) |
THDi (rated power) | < 3% |
BATTERY | |
Battery type | Lithium |
Battery voltage range | 180 ~ 820 V |
Max. charge / discharge current | 160 A (80 A × 2) |
EPS (OFF-GRID) OUTPUT | |
Rated EPS output voltage, frequency | 230 / 400 V, 220 / 380 V, 50 Hz / 60 Hz |
Rated EPS output power | 60.0 kVA |
Peak EPS output power | 66 kVA, continuous 90 kVA, 10s |
Switchover time | < 10 ms |
EFFICIENCY | |
Max. efficiency | 98.0% |
European efficiency | 97.2% |
ENVIRONMENT LIMIT | |
Ingress protection | IP66 |
Operating ambient temperature range④ | -35 ~ 60°C |
Max. operating altitude | 3000 m |
Relative humidity | 0 ~ 100% RH (condensing) |
Overvoltage Category | Mains: Ⅲ, Battery: Ⅱ, PV: Ⅱ |
GENERAL | |
Dimensions (W × H × D) | 820 × 670 × 257 mm |
Net weight | < 105 kg |
X3-AELIO-61K | |
PV INPUT | |
Max. recommended PV array power | 120 kWp |
Max. PV input voltage① | 1000 V |
Nominal PV input voltage | 650 V |
MPPT voltage range② | 160 ~ 950 V |
Start-up voltage | 200 V |
No. of MPP trackers / Strings per MPP tracker | 6 / 2 |
Max. input current per MPPT | 40 A |
Max. input short circuit current per MPPT | 50 A |
AC INPUT & OUTPUT (ON-GRID) | |
Rated output power | 61 kW |
Rated output current | 88.4 A(88A) |
Max. output apparent power | 66 kVA |
Max. output continuous current | 100.0 A(100.3A) |
Nominal AC voltage | 3 / N / PE, 220 / 380 V 3 / N / PE, 230 / 400 V |
Nominal AC frequency | 50 Hz / 60 Hz |
AC frequency range③ | 50 ± 5 Hz / 60 ± 5 Hz |
Adjustable Power Factor range | ~ 1 (0.8 lagging to 0.8 leading) |
THDi (rated power) | < 3% |
BATTERY | |
Battery type | Lithium |
Battery voltage range | 180 ~ 820 V |
Max. charge / discharge current | 160 A (80 A × 2) |
EPS (OFF-GRID) OUTPUT | |
Rated EPS output voltage, frequency | 230 / 400 V, 220 / 380 V, 50 Hz / 60 Hz |
Rated EPS output power | 61.0 kVA |
Peak EPS output power | 66 kVA, continuous 90 kVA, 10s |
Switchover time | < 10 ms |
EFFICIENCY | |
Max. efficiency | 98.0% |
European efficiency | 97.2% |
ENVIRONMENT LIMIT | |
Ingress protection | IP66 |
Operating ambient temperature range④ | -35 ~ 60°C |
Max. operating altitude | 3000 m |
Relative humidity | 0 ~ 100% RH (condensing) |
Overvoltage Category | Mains: Ⅲ, Battery: Ⅱ, PV: Ⅱ |
GENERAL | |
Dimensions (W × H × D) | 820 × 670 × 257 mm |
Net weight | < 105 kg |