200% PV oversize, 15.2kWdc
3 strings MPPT
150% Max. MPPT power
16A Max. input current
100% backup power with grid-tie
Built-in RGM meter
Up to 4 inverter parallel
Peak efficiency(PV-GRID): 98%
Our expertly designed products seamlessly integrate with your existing photovoltaic system, allowing you to connect up to four systems in parallel. Create ample storage with our stackable battery modules T-BAT-SYS-HV-5.0, providing 80kWh of energy for extended power usage. Our system provides multiclass loads management, classifying home loads to prioritize essential ones that meet customers' needs. Embrace the versatility of microgrid operation, wide temperature range, and flexible whole home or partial backup options. With automatic black start and integrated arc fault protection, safety and peace of mind are assured. Experience the true power of our hybrid, AC coupled inverter, and battery systems, revolutionizing your energy management with ease.
Specifications | A1-Hybrid-3.8-G2 |
Max. recommended PV power [W] | 7600 |
Max. MPPT power [W] | 5700 |
Max. DC voltage [V] | 550 |
Max. input current [A] | A: 20 / B: 20 |
Start input voltage [V] | 120 |
No. of MPP trackers | 2 |
Strings per MPP tracker | A: 1 / B: 1 |
DC disconnection switch | YES |
AFCI | YES |
Nominal AC power [VA] | 3816 |
Max. apparent AC power [VA] | 3816 |
Rated grid voltage (AC voltage range) [V] | 240 |
Rated grid Frequency [Hz] | 60 |
Nominal AC current [A] | 15.9 |
Max. AC current [A] | 15.9 |
Maximum output fault current and duration [A/ms] | 17.5 / 20 |
Displacement power factor | 0.8 leading to 0.8 lagging |
Total harmonic distortion (THD, rated power) | < 3% |
Parallel operation | YES |
Dimensions with safety switch (WxHxD) [in (mm)] | 33.1 in x 15.7 in x 5.7 in (840 mm x 400 mm x 145 mm) |
Weight with safety switch [lb (kg)] | 75 lbs (34 kg) |
Warranty | 10 years |
Specifications | A1-Hybrid-5.0-G2 |
Max. recommended PV power [W] | 10000 |
Max. MPPT power [W] | 7500 |
Max. DC voltage [V] | 550 |
Max. input current [A] | A: 20 / B: 20 |
Start input voltage [V] | 120 |
No. of MPP trackers | 2 |
Strings per MPP tracker | A: 1 / B: 1 |
DC disconnection switch | YES |
AFCI | YES |
Nominal AC power [VA] | 5016 |
Max. apparent AC power [VA] | 5016 |
Rated grid voltage (AC voltage range) [V] | 240 |
Rated grid Frequency [Hz] | 60 |
Nominal AC current [A] | 20.9 |
Max. AC current [A] | 20.9 |
Maximum output fault current and duration [A/ms] | 23 / 20 |
Displacement power factor | 0.8 leading to 0.8 lagging |
Total harmonic distortion (THD, rated power) | < 3% |
Parallel operation | YES |
Dimensions with safety switch (WxHxD) [in (mm)] | 33.1 in x 15.7 in x 5.7 in (840 mm x 400 mm x 145 mm) |
Weight with safety switch [lb (kg)] | 75 lbs (34 kg) |
Warranty | 10 years |
Specifications | A1-Hybrid-6.0-G2 |
Max. recommended PV power [W] | 10000 |
Max. MPPT power [W] | 9000 |
Max. DC voltage [V] | 550 |
Max. input current [A] | A: 16 / B: 16 |
Start input voltage [V] | 120 |
No. of MPP trackers | 2 |
Strings per MPP tracker | A: 1 / B: 1 |
DC disconnection switch | YES |
AFCI | YES |
Nominal AC power [VA] | 6000 |
Max. apparent AC power [VA] | 6000 |
Rated grid voltage (AC voltage range) [V] | 240 |
Rated grid Frequency [Hz] | 60 |
Nominal AC current [A] | 25 |
Max. AC current [A] | 25 |
Maximum output fault current and duration [A/ms] | 27.5 / 20 |
Displacement power factor | 0.8 leading to 0.8 lagging |
Total harmonic distortion (THD, rated power) | < 3% |
Parallel operation | YES |
Dimensions with safety switch (WxHxD) [in (mm)] | 33.1 in x 15.7 in x 5.7 in (840 mm x 400 mm x 145 mm) |
Weight with safety switch [lb (kg)] | 75 lbs (34 kg) |
Warranty | 10 years |
Specifications | A1-Hybrid-7.6-G2 |
Max. recommended PV power [W] | 15200 |
Max. MPPT power [W] | 11400 |
Max. DC voltage [V] | 550 |
Max. input current [A] | A: 20 / B: 20 / C: 20 |
Start input voltage [V] | 120 |
No. of MPP trackers | 3 |
Strings per MPP tracker | A: 1 / B: 1 / C: 1 |
DC disconnection switch | YES |
AFCI | YES |
Nominal AC power [VA] | 7608 |
Max. apparent AC power [VA] | 7608 |
Rated grid voltage (AC voltage range) [V] | 240 |
Rated grid Frequency [Hz] | 60 |
Nominal AC current [A] | 31.7 |
Max. AC current [A] | 31.7 |
Maximum output fault current and duration [A/ms] | 34.9 / 20 |
Displacement power factor | 0.8 leading to 0.8 lagging |
Total harmonic distortion (THD, rated power) | < 3% |
Parallel operation | YES |
Dimensions with safety switch (WxHxD) [in (mm)] | 33.1 in x 15.7 in x 5.7 in (840 mm x 400 mm x 145 mm) |
Weight with safety switch [lb (kg)] | 75 lbs (34 kg) |
Warranty | 10 years |