SolaX Power Network Technology (Zhejiang) Co.,Ltd.
SolaX Power Network Technology (Zhejiang) Co.,Ltd.
ENGLISH(GLOBAL)
x3 ultra 1
x3 ultra 2
x3 ultra 3
Hybrid Inverter

X3 ULTRA
X3 ULTRA

X3 ULTRA

15kW / 19.9kW 

20kW / 25kW / 30kW

High Yield & Full Utilization


  • Max. 36A DC input per MPPT

  • 3 MPPT, 6 Strings

  • 200% PV Oversizing

  • Max. 200% PV Input


Money Saving


  • 100% Unbalanced Output

  • 7X24 Time of Use (ToU)


AI-Driven Energy Management


  • Smart Schedule

  • Smart Scene

  • Intelligent loads management

Dual Independent Battery Ports


  • Managed independently for easy expansion

  • Dual ports can be paralleled to connect

  • one large capacity battery.

  • Up to 2.8MWh with TB-PBOX*


High Safety & Reliability


  • AFCI optional

  • Type II SPD on AC&DC side


Robust Backup


  • <10ms switchover time

  • 2Pn EPS overload for 10 sec

  • All types of loads supported 

  • Micro-grid supported 

  • Diesel generator supported

Why X3 ULTRA

Introduces a new C&I energy storage solution, suitable for factories, malls, offices, and warehouse. 

With 2/3 MPPTs, it maximizes power generation, enhancing compatibility with complex solar systems. 

Even if one MPPT encounters a fault, it won't affect the operation of other arrays.


200% oversized PV input = 100% AC Output + 100% Battery Storage

We ensure every unit of solar power is fully utilized, converted into AC output and stored in batteries efficiently. 

Power is allocated independently to each phase, controllable down to 0W per phase, with a max.10kW output on a single phase, reducing grid reliance.


Highlighting our micro-gird function. 

The micro-grid feature enables the hybrid inverter to simulate the grid and activate the string inverter when off-grid. 

By connecting the string inverter to the hybrid inverter's EPS port, it can use PV or battery energy to power the string inverter during utility outages.


Leveraging real-time data detection through our SOLAX Cloud streamlines commercial and industrial management processes.


15kW
15KP
19.9kW
20kW
20KP
25kW
30kW
ModelX3-ULT-15K
INPUT PV
Max.recommended PV array power [Wp]30000
Max.input DC power [W]30000
Max.DC voltage [V]①1000
Norminal DC operating voltage [V]600
No. of MPP trackers / Strings per MPP tracker2 ( 2 / 2 )
Max. input current ( input  PV1/ input PV2/input PV3) [A]②36 / 36
Max. short circuit current ( input  PV1/ input PV2/input PV3) [A]②45 / 45
MPPT voltage range [V]③160 - 950
Start output voltage [V]200
OUTPUT AC (On - Grid)
Norminal AC power [VA]15000 (AS4777 14999)
Max. apparent AC power [VA]16500 (AS4777 14999)
Rated grid voltage (AC voltage range) [V]3P4W,  400 / 230
Rated grid Frequency [Hz]50 / 60
Norminal AC current [A]21.8
Max. AC current [A]24.0(AS4777 21.8)
Displacement power factor1 ( - 0.8 ~ 0.8)
Total harmonic distortion(THDi,  rated power) [%]< 3
INPUT AC
Norminal AC power [VA]15000
Norminal AC current [A]21.8 
Rated grid voltage(AC voltage range) [V]3P4W,  400 / 230
Rated grid Frequency [Hz]50 / 60
BATTERY
Battery typeLithium - ion
Battery voltage range [V] 120 - 800
Max.charge / discharge current [A]60 ( 30 * 2 )
EPS OUTPUT(WITH BATTERY)
EPS peak  power [VA]2 times of rated power, 10s
EPS rated  power [VA]15000
EPS rated voltage [V], Frequency [Hz] 400 / 230; 50 / 60
EPS rated current [A]21.8 
Switch time [ms]< 10
Total harmonic distortion(THDv,  linear Load)  [%]< 3


ModelX3-ULT-15KP
INPUT PV
Max.recommended PV array power [Wp]30000
Max.input DC power [W]30000
Max.DC voltage [V]①1000
Norminal DC operating voltage [V]600
No. of MPP trackers / Strings per MPP tracker3 ( 2 / 2 / 2 )
Max. input current ( input  PV1/ input PV2/input PV3) [A]②36 / 36 / 36
Max. short circuit current ( input  PV1/ input PV2/input PV3) [A]②45 / 45 / 45
MPPT voltage range [V]③160 - 950
Start output voltage [V]200
OUTPUT AC (On - Grid)
Norminal AC power [VA]15000 (AS4777 14999)
Max. apparent AC power [VA]16500 (AS4777 14999)
Rated grid voltage (AC voltage range) [V]3P4W,  400 / 230
Rated grid Frequency [Hz]50 / 60
Norminal AC current [A]21.8
Max. AC current [A]24.0(AS4777 21.8)
Displacement power factor1 ( - 0.8 ~ 0.8)
Total harmonic distortion(THDi,  rated power) [%]< 3
INPUT AC
Norminal AC power [VA]15000
Norminal AC current [A]21.8 
Rated grid voltage(AC voltage range) [V]3P4W,  400 / 230
Rated grid Frequency [Hz]50 / 60
BATTERY
Battery typeLithium - ion
Battery voltage range [V] 120 - 800
Max.charge / discharge current [A]60 ( 30 * 2 )
EPS OUTPUT(WITH BATTERY)
EPS peak  power [VA]2 times of rated power, 10s
EPS rated  power [VA]15000
EPS rated voltage [V], Frequency [Hz] 400 / 230; 50 / 60
EPS rated current [A]21.8 
Switch time [ms]< 10
Total harmonic distortion(THDv,  linear Load)  [%]< 3


ModelX3-ULT-19.9K
INPUT PV
Max.recommended PV array power [Wp]40000
Max.input DC power [W]40000
Max.DC voltage [V]①1000
Norminal DC operating voltage [V]600
No. of MPP trackers / Strings per MPP tracker2 ( 2 / 2 )
Max. input current ( input  PV1/ input PV2/input PV3) [A]②36 / 36
Max. short circuit current ( input  PV1/ input PV2/input PV3) [A]②45 / 45
MPPT voltage range [V]③160 - 950
Start output voltage [V]200
OUTPUT AC (On - Grid)
Norminal AC power [VA]19999
Max. apparent AC power [VA]19999
Rated grid voltage (AC voltage range) [V]3P4W,  400 / 230
Rated grid Frequency [Hz]50 / 60
Norminal AC current [A]29.0
Max. AC current [A]29.0
Displacement power factor1 ( - 0.8 ~ 0.8)
Total harmonic distortion(THDi,  rated power) [%]< 3
INPUT AC
Norminal AC power [VA]19999
Norminal AC current [A]29.0 
Rated grid voltage(AC voltage range) [V]3P4W,  400 / 230
Rated grid Frequency [Hz]50 / 60
BATTERY
Battery typeLithium - ion
Battery voltage range [V] 120 - 800
Max.charge / discharge current [A]60 ( 30 * 2 )
EPS OUTPUT(WITH BATTERY)
EPS peak  power [VA]2 times of rated power, 10s
EPS rated  power [VA]19999
EPS rated voltage [V], Frequency [Hz] 400 / 230; 50 / 60
EPS rated current [A]29.0 
Switch time [ms]< 10
Total harmonic distortion(THDv,  linear Load)  [%]< 3


ModelX3-ULT-20K
INPUT PV
Max.recommended PV array power [Wp]40000
Max.input DC power [W]40000
Max.DC voltage [V]①1000
Norminal DC operating voltage [V]600
No. of MPP trackers / Strings per MPP tracker2 ( 2 / 2 )
Max. input current ( input  PV1/ input PV2/input PV3) [A]②36 / 36
Max. short circuit current ( input  PV1/ input PV2/input PV3) [A]②45 / 45
MPPT voltage range [V]③160 - 950
Start output voltage [V]200
OUTPUT AC (On - Grid)
Norminal AC power [VA]20000
Max. apparent AC power [VA]22000
Rated grid voltage (AC voltage range) [V]3P4W,  400 / 230
Rated grid Frequency [Hz]50 / 60
Norminal AC current [A]29.0
Max. AC current [A]31.9 
Displacement power factor1 ( - 0.8 ~ 0.8)
Total harmonic distortion(THDi,  rated power) [%]< 3
INPUT AC
Norminal AC power [VA]20000
Norminal AC current [A]29.0 
Rated grid voltage(AC voltage range) [V]3P4W,  400 / 230
Rated grid Frequency [Hz]50 / 60
BATTERY
Battery typeLithium - ion
Battery voltage range [V] 120 - 800
Max.charge / discharge current [A]60 ( 30 * 2 )
EPS OUTPUT(WITH BATTERY)
EPS peak  power [VA]2 times of rated power, 10s
EPS rated  power [VA]20000
EPS rated voltage [V], Frequency [Hz] 400 / 230; 50 / 60
EPS rated current [A]29.0 
Switch time [ms]< 10
Total harmonic distortion(THDv,  linear Load)  [%]< 3


ModelX3-ULT-20KP
INPUT PV
Max.recommended PV array power [Wp]40000
Max.input DC power [W]40000
Max.DC voltage [V]①1000
Norminal DC operating voltage [V]600
No. of MPP trackers / Strings per MPP tracker3 ( 2 / 2 / 2 )
Max. input current ( input  PV1/ input PV2/input PV3) [A]②36 / 36 / 36
Max. short circuit current ( input  PV1/ input PV2/input PV3) [A]②45 / 45 / 45
MPPT voltage range [V]③160 - 950
Start output voltage [V]200
OUTPUT AC (On - Grid)
Norminal AC power [VA]20000
Max. apparent AC power [VA]22000
Rated grid voltage (AC voltage range) [V]3P4W,  400 / 230
Rated grid Frequency [Hz]50 / 60
Norminal AC current [A]29.0
Max. AC current [A]31.9 
Displacement power factor1 ( - 0.8 ~ 0.8)
Total harmonic distortion(THDi,  rated power) [%]< 3
INPUT AC
Norminal AC power [VA]20000
Norminal AC current [A]29.0 
Rated grid voltage(AC voltage range) [V]3P4W,  400 / 230
Rated grid Frequency [Hz]50 / 60
BATTERY
Battery typeLithium - ion
Battery voltage range [V] 120 - 800
Max.charge / discharge current [A]60 ( 30 * 2 )
EPS OUTPUT(WITH BATTERY)
EPS peak  power [VA]2 times of rated power, 10s
EPS rated  power [VA]20000
EPS rated voltage [V], Frequency [Hz] 400 / 230; 50 / 60
EPS rated current [A]29.0 
Switch time [ms]< 10
Total harmonic distortion(THDv,  linear Load)  [%]< 3



ModelX3-ULT-25K
INPUT PV
Max.recommended PV array power [Wp]50000
Max.input DC power [W]50000
Max.DC voltage [V]①1000
Norminal DC operating voltage [V]600
No. of MPP trackers / Strings per MPP tracker3 ( 2 / 2 / 2 )
Max. input current ( input  PV1/ input PV2/input PV3) [A]②36 / 36 / 36
Max. short circuit current ( input  PV1/ input PV2/input PV3) [A]②45 / 45 / 45
MPPT voltage range [V]③160 - 950
Start output voltage [V]200
OUTPUT AC (On - Grid)
Norminal AC power [VA]25000 (VDE4105 24900)
Max. apparent AC power [VA]27500 (VDE4105 24900)
Rated grid voltage (AC voltage range) [V]3P4W,  400 / 230
Rated grid Frequency [Hz]50 / 60
Norminal AC current [A]36.3
Max. AC current [A]39.9 (VDE4105 36.3)
Displacement power factor1 ( - 0.8 ~ 0.8)
Total harmonic distortion(THDi,  rated power) [%]< 3
INPUT AC
Norminal AC power [VA]25000
Norminal AC current [A]36.3 
Rated grid voltage(AC voltage range) [V]3P4W,  400 / 230
Rated grid Frequency [Hz]50 / 60
BATTERY
Battery typeLithium - ion
Battery voltage range [V] 120 - 800
Max.charge / discharge current [A]60 ( 30 * 2 )
EPS OUTPUT(WITH BATTERY)
EPS peak  power [VA]2 times of rated power, 10s
EPS rated  power [VA]25000
EPS rated voltage [V], Frequency [Hz] 400 / 230; 50 / 60
EPS rated current [A]36.3 
Switch time [ms]< 10
Total harmonic distortion(THDv,  linear Load)  [%]< 3


ModelX3-ULT-30K
INPUT PV
Max.recommended PV array power [Wp]60000
Max.input DC power [W]60000
Max.DC voltage [V]①1000
Norminal DC operating voltage [V]600
No. of MPP trackers / Strings per MPP tracker3 ( 2 / 2 / 2 )
Max. input current ( input  PV1/ input PV2/input PV3) [A]②36 / 36 / 36
Max. short circuit current ( input  PV1/ input PV2/input PV3) [A]②45 / 45 / 45
MPPT voltage range [V]③160 - 950
Start output voltage [V]200
OUTPUT AC (On - Grid)
Norminal AC power [VA]30000  (AS4777 29999, VDE4105 29900)
Max. apparent AC power [VA]30000  (AS4777 29999,  VDE4105 29900)
Rated grid voltage (AC voltage range) [V]3P4W,  400 / 230
Rated grid Frequency [Hz]50 / 60
Norminal AC current [A]43.5
Max. AC current [A]43.5 
Displacement power factor1 ( - 0.8 ~ 0.8)
Total harmonic distortion(THDi,  rated power) [%]< 3
INPUT AC
Norminal AC power [VA]30000
Norminal AC current [A]43.5 
Rated grid voltage(AC voltage range) [V]3P4W,  400 / 230
Rated grid Frequency [Hz]50 / 60
BATTERY
Battery typeLithium - ion
Battery voltage range [V] 120 - 800
Max.charge / discharge current [A]60 ( 30 * 2 )
EPS OUTPUT(WITH BATTERY)
EPS peak  power [VA]2 times of rated power, 10s
EPS rated  power [VA]30000
EPS rated voltage [V], Frequency [Hz] 400 / 230; 50 / 60
EPS rated current [A]43.5 
Switch time [ms]< 10
Total harmonic distortion(THDv,  linear Load)  [%]< 3


X3 ULTRA
Documents
Datasheet
Language
English
Format
PDF
Size
1.23M
Last updated
17/07/2024
Language
Português
Format
PDF
Size
363KB
Last updated
25/10/2024
User Manual
Language
English
Format
PDF
Size
62.6M
Last updated
30/10/2024
Language
Italiano
Format
PDF
Size
42.6M
Last updated
14/09/2024
Language
Čeština
Format
PDF
Size
22.0M
Last updated
26/09/2024
Quick Installation
Language
English
Format
PDF
Size
46.4M
Last updated
5/06/2024
Language
Čeština
Format
PDF
Size
4.4M
Last updated
26/09/2024
Feedback
Info
Role
Installer
Distributor
End User
Others
Further information can be found in the privacy policy. I understand that I can withdraw my consent at any time.
I agree with SolaX data protection directive
SolaX Power Network Technology (Zhejiang) Co.,Ltd.
We use cookies to optimise and personalise your experience, but you can choose to opt out of non-essential cookies.
To find out more, read our Privacy Policy and Terms of Use
Reject All
Accept All
Leave Your Message